Page contents
  1. How do I calculate the Kv of a valve and its authority?
  2. Kv and valve authority formulas
  3. Pressure drop of a valve of Kvs 10 against water flow rate
  4. Valve authority against its Kvs, for 8 m³/h and a…
  5. Kv, Kvs, Cv and valve authority calculator
  6. Detailed explanations and calculation in Mecaflux
  7. Frequently asked questions

How do I calculate the Kv of a valve and its authority?

The Kv of a valve is the water flow rate, in m³/h, that passes through it under a pressure drop of 1 bar at a given opening; the Kvs is the Kv at full opening, and the Cv its imperial equivalent (US gallons per minute under 1 psi), with Cv = 1.156 Kv. The defining relation, Q = Kv × √(ΔP / d) (Q in m³/h, ΔP in bar, d relative density of the liquid to water), gives any of the three quantities from the other two. The authority of the valve, a = ΔPvalve open / (ΔPvalve open + ΔPcontrolled circuit), measures its ability to control the flow: the target is 0.5. Example: a valve of Kvs 10 passing 8 m³/h of water loses ΔP = (8/10)² = 0.64 bar; if the circuit it controls loses 0.5 bar at that flow rate, its authority is 0.64 / (0.64 + 0.5) = 0.56, which is suitable. The calculator below gives the missing Kv, flow rate or pressure drop, the equivalent ζ coefficient, the authority and the ideal Kvs among the standard values.

Kv and valve authority formulas

Q = Kv × √ΔP√d     Kv = Q × √d√ΔP     ΔP = d × Q²Kv²     Cv = 1.156 × Kv     a = ΔPvΔPv + ΔPcircuit     ζ = 0.0016 × DN⁴Kv²
  • Q: flow rate through the valve, in m³/h; ΔP: pressure drop of the valve, in bar; d: relative density of the liquid to water (density / 1,000)
  • Kv: flow coefficient at the opening considered, in m³/h; Kvs: Kv at full opening, the catalogue value, to be used for the authority; Cv: the same coefficient in imperial units
  • a: valve authority, dimensionless, ratio of its fully open pressure drop ΔPv to the total pressure drop of the controlled circuit (valve included) at the same flow rate; target 0.5, acceptable from 0.3 to 0.7
  • ζ: equivalent minor loss coefficient, with DN the nominal diameter in mm, usable in a conventional head loss balance (ΔH = ζ V²/2g)

Pressure drop of a valve of Kvs 10 against water flow rate

ΔP = (Q / Kvs)² in bar for water (d = 1); corresponding Cv: 11.6
Flow rate QΔP of the fully open valveLoss in metres of water
2 m³/h0.04 bar0.41 m
4 m³/h0.16 bar1.63 m
6 m³/h0.36 bar3.67 m
8 m³/h0.64 bar6.53 m
10 m³/h1.00 bar10.2 m
12 m³/h1.44 bar14.7 m
15 m³/h2.25 bar22.9 m

Valve authority against its Kvs, for 8 m³/h and a controlled circuit losing 0.5 bar

Kvs from the standard series (R10); a = ΔPv / (ΔPv + 0.5); the ideal Kvs for a = 0.5 is 11.3 (ΔPv = 0.5 bar)
Valve KvsΔP valve fully openAuthority aAssessment
6.3 m³/h1.61 bar0.76very precise but excessive pressure drop and pumping cost
8 m³/h1.00 bar0.67precise, high pressure drop
10 m³/h0.64 bar0.56good choice
12.5 m³/h0.41 bar0.45acceptable
16 m³/h0.25 bar0.33imprecise control
20 m³/h0.16 bar0.24oversized valve
25 m³/h0.10 bar0.17the valve hardly controls any more

Kv, Kvs, Cv and valve authority calculator

Relation Q = Kv·√(ΔP/d): from two of the three quantities Kv (or Cv), flow rate and pressure drop, the calculator gives the third one, the equivalent loss coefficient ζ and, if you enter the pressure drop of the circuit to be controlled, the valve authority.

Valve and liquid
Valve authority (optional)
Kv and Cv
Pressure drop
Flow rate
Equivalent loss coefficient ζ (ζ = 0.0016·DN⁴/Kv²)

Kv: water flow rate in m³/h that creates a pressure drop of 1 bar at a given opening; Kvs: the same value with the valve fully open, to be used for the authority. Cv = 1.156 × Kv (US gallons per minute at 1 psi). Formulas valid for liquids in turbulent flow, without cavitation or flashing in the valve. Authority = ΔP of the fully open valve / (ΔP valve + ΔP of the controlled circuit), with a target of 0.5 as explained above. Standard Kvs values from the Renard series used by manufacturers. See also the minor losses calculator.

Detailed explanations and calculation in Mecaflux

For controlling the flow of a section , to balance network branches in parallel, or controlling the flow of an oversized pump, we use a valve. How to choose it ?

Authority valve kvs kv cv

The valve must control the flow evenly and not create too much pressure loss to prevent the pumping energy costs. If it is too large it will generate virtually no pressure drop and low cost of pumping, but it will be not very accurate in setting the rate.. If it is too small it will be very accurate but the reduction in diameter will generate a loss, even if the valve is wide open. A good compromise is reached when the pressure drop of the valve is equal to that of the segment that it must control. This ability to regulate the section that you want to vary the flow is called the valve authority. This authority is calculated: Authority=loss of load valve wide open / ( loss of load valve wide open+ Pressure drop of the section, to regulate (at the open valve flow rate )) This authority should be 0.5 to be adequate. This means that the pressure drop of the valve wide open must be equal to that of the section that must be controlled.

With Mecaflux standard :

To test the authority of a valve, calculate its pressure drop wide open and compare it to that of the section in which it should vary the flow..

kv cv loss calculation kvs load Ball Valve

Kv and KVS provide information about the flow that will pass through a valve:
  • KV is the flow that generates a pressure drop of 1 bar at a given degree of openness .
  • KVS is the flow that generates a pressure drop of 1 bar when the valve opening is maximum.
The calculation of valve's KV can therefore be related to the pressure loss

Conversion tool kV KVS and CV valve in mecaflux. This tool is used to test the authority of a valve for a section, which you computed the head loss, or to establish the KV or KVS or CV of a valve according to his head loss ... It is accessible from the tool menu of the software.

autorité de vanne calcul kv cv kvs

Frequently asked questions

What is the difference between Kv, Kvs and Cv?

The Kv varies with the valve opening: each position of the handwheel or actuator corresponds to a Kv, and the curve of Kv/Kvs against travel is the valve characteristic (linear, equal percentage, on-off). The Kvs is the maximum value, valve fully open, the one in catalogues and the one used for sizing and authority. The Cv is the same quantity in US units, in gallons per minute under 1 psi: Cv = 1.156 Kv, i.e. Kv = 0.865 Cv. All three apply to liquids in turbulent flow.

What happens if the authority is too low or too high?

With a low authority (oversized valve), the pressure drop of the valve is negligible compared with that of the circuit: the first per cent of closure hardly change the flow rate, then everything happens at the end of the travel, the control hunts and comfort suffers. With a high authority (undersized valve), the adjustment is very progressive but the valve permanently consumes a pressure the pump has to supply, hence energy, even fully open. The 0.5 compromise, where the fully open valve loses as much as the circuit it controls, is the rule of good practice in heating and air conditioning.

Is the Kv formula valid for a gas or for steam?

No: Q = Kv √(ΔP/d) assumes an incompressible liquid in turbulent flow, without cavitation or flashing in the valve. For air, a gas or steam, manufacturers give Kv formulas involving the upstream absolute pressure, the temperature and the density at normal conditions, with a choked (sonic) flow regime when the downstream pressure falls below half the upstream pressure. For a liquid close to its boiling point, the risk of cavitation in the valve must also be checked, since the pressure drops sharply through the seat.

How do I select and check the control valves of my own network?

Mecaflux Standard includes the Kv, Kvs and Cv conversion tool and calculates the pressure drop of each valve fully open, to be compared with that of the controlled circuit to obtain the authority. For a branched network with its balancing valves, Mecaflux Pro3D, as a stand-alone licence, models the valves and branches in 3D and balances the circuits. Mecaflux also carries out the study of your project and delivers the calculation report, or offers training on the software applied to your own network.